1. Output low-voltage / High-voltage protection Built-in low-voltage / high-voltage detection and protection circuit. Protection points adjustable. When output
voltage is out of range, protector will cut off output and give warning (LED Blinking).
2. Open-phase protection Built-in Open-phase protection circuit. When Open-phase happens, protector will cut off output and give
warning (LED Blinking).
3. Overload protection Built-in overload protection will protect this AVR automatically even the output was short circuit.
4. Superior monitoring system Even with the mentioned built-in protection inside, we integrated a Superior monitoring System to give double insurance of the performance.
5. Soft-output function Built-in Soft-output function, when started or resume form power outages, output voltage will be started from a low voltage to avoid damage to equipments.
6. Free form Voltage-Drop Dual-stack design. Even a single phase loading is imbalance up to 50%, Voltage-Drop will not happen. So it is ideal for motor, servo motor and other launch-frequent equipments.
7. Pure Linear Voltage adjustment Linear Induction control, no voltage ladder. (Relay type and servo motor type can only give ladder voltage output)
8. Contactless design No contact surface in the machine, no Arc.
9. Wide input voltage range ±15% or ±30% input voltage range.
10. Modular design Complete Modular design, for easy after sales services and debugging.
11. Fully isolated, manual bypass function For maintenance or repairs, bypass can be activated manually (short-circuit and overload protection are still
on guard)
12. High temperature detection Built-in temperature detection circuit, when main coils are overheating LED blinking will be activated, giving message that maintenance or replacement of the mail coils required.
13. Misoperation prevention design To prevent misoperation, double lock system was applied in this AVR. Only press the two power buttons in the same time can the machine be started or shut down.
14. Excellent loading / overloading ability 100% load for continuous operation, transient inductive loading is also welcome.
15. Better efficiency, excellent characteristics high efficiency low iron loss Silicon steel was applied, the base of lowest reactive loss and active loss.
16. Compact size design The high-strength structural design gives a smaller size and less weight.
17. Seriously selected industrial-strength components, work for more than 10 years Lifespan can be more than 10 years. All components are selected for years, transient high voltage is welcome.
**RS-232/485 optional
|
Input
|
Input Voltage Range
|
±15% for ARD series ±30% for ARD series
|
|
Input Frequency
|
45~65Hz
|
|
Output
|
Output Voltage Range
|
±1%~±5% adjustable
|
|
Output Accuracy
|
±2%
|
|
Efficiency
|
98% at full load
|
|
Phase
|
three phase
|
|
Overload Ability
|
At rated current, 5 seconds for 500% load; 30 seconds for 300% load; 60 seconds for 200% load
|
|
Head Run
|
<100°C at full load
|
|
Wave Distortion
|
<3% insulation resistance; coil to ground ≥5MΩ
|
|
Respond Time
|
<0.042 second
|
|
Insulation Withstanding
|
2000V 60S (coil to other body)
|
|
Creepage Distance
|
>8mm
|
|
Grounding Resistance
|
≤0.1 MΩ
|
|
Overheat Bypass
|
Main coil temperature >130°C, transfer to bypass automatically
|
|
Protection
|
Input low voltage, output high voltage, open fase
|
|
Energy Saving Function
|
Automatic power cut off without loading
|
|
Delay Function
|
yes
|
|
No-load Loss
|
≤1%
|
|
Cooling Mode
|
Forced cooling by air
|
|
Fan Activated Temperature
|
100°C
|
|
Shock Resistant
|
0.3G
|
|
Noise
|
≤65dB (at 1 meter from cabinet with full load
|
|
Operation Humidity
|
0%~90%, non-condensing
|
|
Operation Temperature
|
-20°C~40°C
|
|
Model
|
Size (cm)
|
Capacity (KW)
|
Weight (kgs)
|
|
| |
|
ARD-10KVA
|
28×38×62
|
8
|
50
|
|
|
ARD-15KVA
|
12
|
58
|
|
|
ARD-20KVA
|
36×46×81
|
16
|
85
|
|
|
ARD-30KVA
|
24
|
100
|
|
|
ARD-45KVA
|
36
|
115
|
|
|
ARD-60KVA
|
42×55×96
|
48
|
140
|
|
|
ARD-80KVA
|
64
|
165
|
|
|
ARD-100KVA
|
80
|
230
|
|
|
ARD-120KVA
|
55×80×170
|
96
|
620
|
|
|
ARD-150KVA
|
120
|
750
|
|
|
ARD-200KVA
|
160
|
900
|
|
|
HRD-45KVA
|
80×55×100
|
36
|
240
|
|
|
HRD-60KVA
|
48
|
280
|
|
|
HRD-80KVA
|
64
|
320
|
|
|
HRD-120KVA
|
55×80×170
|
96
|
620
|
|
|
HRD-150KVA
|
120
|
750
|
|
|
HRD-200KVA
|
160
|
900
|
|
|